|

| Flat Tape System | Solid Circular System | Cable and Wire System | Accessories |

| How to apply lightning protection |


Structural lightning protection design considerations

Down conductors

furse

Down conductor positioning and distancing is often dictated by architectural constraints. There should be one down conductor for every 20m or part there of of the building perimeter at roof or ground level (whichever is greater).These should be evenly spaced and distances apart of more than 20m avoided if possible.

If the building is above 20m in height or of an abnormal risk this distance should be reduced to 10m.

They should be routed as directly as possible from the air termination network to the earth termination network to avoid risks of side flashing. Re-entrant loops are also to be avoided. BS 6651 recommends that the length of conductor forming the loop should not exceed eight times the width of its open side.

BS 6651 allows the use of `natural conductors' such as rebars and structural steelwork, provided that they are electrically continuous and adequately earthed.

click image to enlarge
Figure 3 - Lightning Protection Scheme to BS 6651 using the reinforced concrete within the structure for down conductors.

Figure 3 - Lightning Protection Scheme to BS 6651 using the reinforced concrete within the structure for down conductors.


BS 6651 allows the use of `natural conductors'such as rebars and structural steelwork, provided that they are electrically continuous and adequately earthed.

 

Earth termination networks

Each down conductor must have a separate earth termination. Moreover provision should be made in each down conductor, for disconnection from the earth for testing purposes.This is achieved with a test clamp (see Figure 4).



Figure 4 - Oblong test or junction clamp
Figure 4 - Oblong test or junction clamp

BS 6651 stipulates that the resistance to earth of the lightning protection system measured at any point, should not exceed 10 ohms.

With the test clamp disconnected, the resistance of each individual earth should be no more than ten times the number of down conductors in the complete system. eg for a system with 15 down conductors, the individual earth readings should be no more than 10 x 15 = 150 ohms.

Several types of earth electrode are permissible, but by far the most commonly used are deep driven earth rods. BS 6651 states that the combined earth rod length of a system should be no less than 9m whilst each individual earth rod should be no less than 1.5m in length.



Figure 5 - Deep driven earth electrode
Figure 5 - Deep driven earth electrode

|

| Flat Tape System | Solid Circular System | Cable and Wire System Accessories |

| How to apply lightning protection |
|