Type 100/101X Electro Mechanical Converters Current to Pressure (I/P) and Voltage to Pressure (E/P) Features
Reliable, rugged The 100/101X series offers a range of reliable
instruments and many thousands of units are installed worldwide each
year. The units are uncomplicated by design, making use of electromagnetic
force balance technology with flapper valve control and potentiometer
adjustment. |
|
Pneumatic | ||
*Output Signal | See product selector | |
*Air Supply | Oil free, dry air, filtered to 5 microns; at least 0.7bar above maximum required output pressure range | |
*Flow Capacity | Up to 300Nl/min (10scfm) | |
*Air Consumption | < 4bar: 0.85 l/min (0.03scfm)
typical > 4bar: 1.75 l/min (0.06scfm) typical |
|
*Response Time (dependent on input and output pressure) | < 2bar/30psig: less than 0.5 seconds
for 10-90% step change > 2bar/30psig: 2 seconds for 10-90% step change |
|
*Total Error | +/-0.5% of span (typical, independent error includes the combined effect of non-linearity, hysteresis, deadzone and repeatability) | |
*Temperature Effect | Typically better than 0.1% span/°C for span and zero over operating range | |
*Supply Sensistivity | Better than 0.025% span output change per % supply pressure change | |
*Connections | 1/4" NPT standard (others available on request) | |
Physical | ||
*Operating Temperature | -20°C to +70°C | |
*IP Rating | IP65 in normal operation | |
*Electromagnetic Compatibility | This is a passive electromagnetic instrument and is unaffected by interfering high frequency signals | |
*Material of Construction | Zinc diecasting passivated and epoxy paint, nitrile diaphragms, stainless steel/nylon flapper nozzle and supply valve | |
*Mass | 1500g | |
*Mounting Position | Integral surface mounting bracket provided for preferred vertical mounting. 50mm pipe mounting kit available | |
Electrical | ||
*Electrical Signal | See product selector | |
*Failure Mode | Signal falls to bleed pressure when electrical supply fails | |
*Connections | 30mm square connector DIN 43650 provided, mountable in four directions (alternative connections available) |
|
|
Certification | ||
An intrinsically safe 100X model certified to
CENELEC EN50 020 (BS 5501 part 7) EEx ia llC T4 is available (Installation
with these models must comply with information given in BS 5345, parts
1 and 4) |
Ordering Information
|
Electronic I/P Converters |
Want A Quotation? |